Winding
HomeHome > News > Winding

Winding

Aug 15, 2023

Scientific Reports volume 12, Article number: 20157 (2022) Cite this article

962 Accesses

Metrics details

Power transformers are important equipment in power systems and require a responsive and accurate protection system to ensure system reliability. In this paper, a fault location algorithm for power transformers based on the discrete wavelet transform and back-propagation neural network is presented. The system is modelled on part of Thailand's transmission and distribution system. The ATP/EMTP software is used to simulate fault signals to validate the proposed algorithm, and the performance is evaluated under various conditions. In addition, various activation functions in the hidden and output layers are compared to select suitable functions for the algorithm. Test results show that the proposed algorithm can correctly locate faults on the transformer winding under different conditions with an average error of less than 0.1%. This result demonstrates the feasibility of implementing the proposed algorithm in actual protection systems for power transformers.

Power transformers, which are essential equipment in power systems, enable the transmission of power between different sections of the network at different voltages. Owing to increased power consumption in the past decade as a result of urbanisation and economic growth, power systems and interconnected power grids have expanded rapidly and become more complex. Power transformers, which play a significant role in these changes, are vulnerable to faults and decrease network reliability. Thus, it is important to establish a protection system to accurately identify faults and isolate them from the system. Locating faults during fault diagnosis can also help operation and maintenance crews respond correctly to faults in power transformers. Winding faults are common in power transformers; they occur inside the transformer and are caused by the degradation of the winding insulation1,2. If the fault cannot be addressed quickly and correctly, it can irreparably damage the transformer. Power transformers are typically protected using a combination of overcurrent relays, pressure relays, and differential relays3. The Electricity Generating Authority of Thailand (EGAT) currently uses conventional methods to diagnosis faults in power transformers, such as dissolved gas analysis4, frequency response analysis (FRA)5, and winding impedance measurements6. These methods, which have both advantages and disadvantages, can be improved to increase system efficiency and reliability.

Fault analysis has been studied using various techniques to successfully detect, identify, and locate faults in power systems. An interturn fault detection system that uses a primary-side neutral current to indicate fault status has been implemented in power transformers7. No-load active power loss and reactive power can be applied to detect interturn faults in power transformers8. Using current harmonics as a determining factor, they can correctly detect whether a power transformer is in a fault state9,10. A protection system based on the Internet of things can monitor and analyse an obtained signal11. For transformer, winding-to-ground fault is an abnormal condition that may lead to damage of the equipment, which is the reason many research has been analysis it characteristic in order to diagnosis it correctly12,13. However, implementation is limited because such systems require additional components or are not suitable for specific applications. Thus, mathematical tools have been used to obtain an improved algorithm with broader applicability.

The wavelet transform is a mathematical tool can be used to analyse signals for various purposes. In power system applications, it can overcome the disadvantages of the Fourier transform for signal analysis. The mother wavelet used in the analysis also affects the performance of algorithms, and the performance of various mother wavelets in power system applications has been compared to select the optimal mother wavelet for fault analysis. A previous study illustrated that Daubechies wavelets are suitable for the analysis of transient fault conditions14,15. A wavelet-based algorithm for power transformer differential protection correctly detected different types of fault16. The continuous wavelet transform has also been implemented by processing the FRA signal to identify winding deformation17. Another wavelet-based detection algorithm that requires only the high-frequency components detected earth faults with similar accuracy18. The characteristic of the coefficient value also presented in previous work, which demonstrated that this characteristic can be used to for fault diagnosis application19. These applications have provided insight into the suitability of wavelets as a mathematical tool to analyse transient fault signals. However, improved accuracy is desirable.

In recent years, artificial intelligence are another tool that has been widely used and able to changing the way interact with the world20; methods such as support vector machine21, decision tree22, and artificial neural networks (ANNs)9,23,24 are often employed. Various neural networks provide different suitable objectives and applications. For example, the PNN suitable for is widely used in classification and pattern recognition problems. Convolutional neural network (CNN) is a class of artificial neural network (ANN), most commonly applied to analyze visual imagery. Long short-term memory (LSTM) is an artificial neural network used in the fields of artificial intelligence and deep learning. The application of LSTM for example is handwriting recognition, speech recognition, video games etc. Although there are many types of neural networks, only a few neuron-based structures are commonly used for solving various power system problems. In the case of back-propagation neural network (BPNN), it is one of the first kind of neural networks that are widely researched and applied for fault detection owing to its effectiveness to solve almost all types of problems and do not require a rapid response, such as fault detection, design optimization, and not very short-term forecasting, and its ability to detect, classify, and locate faults in power systems has been demonstrated25,26,27. The success of BPNN is owning to the process of calculating the error and propagating back to the network by an optimizer, which provides very accurate results. From the previous research, we used BPNN to classify internal and external faults in power systems with the power transformer, which can be achieved satisfy accuracy28. In addition, the activation functions used in BPNNs provide flexibility for different applications29. Its functionalities make it preferable to other neural network types.

A literature review revealed that power transformer faults can significantly affect network operation. Thus, an accurate fault locating algorithm can help operation and maintenance crews address the issue correctly and quickly. However, most studies have focused on the effects of the magnetising inrush current and the discrimination of the magnetising inrush current from internal faults, including fault classification. However, the detection of the locations of winding-to-ground faults is rarely discussed. The ability to identify fault locations along transformer windings would be highly useful. Therefore, this study investigated a method of locating winding-to-ground faults in a two-winding three-phase transformer that requires less complex analysis than conventional methods.

This paper proposes an algorithm for detecting and locating winding-to-ground faults using a wavelet transform and BPNN. To evaluate the performance of the algorithm, the ATP/EMTP software30 was used to simulate a power transformer and generate fault signals in a system modelled on an actual EGAT two-winding three-phase transformer in Thailand. Figure 1 shows a simplified flowchart of the proposed algorithm, which can send signals to a trip relay and locate a fault in a power transformer winding. The algorithm uses the current waveform obtained from monitoring units on windings of various sizes and applies a discrete wavelet transform (DWT) to extract the coefficients of the first scale. The comparison coefficient is used as the input for training the neural network. Suitable combinations of activation functions for the hidden layers and output layer of the BPNN are also selected.

Diagram of power transformer fault detection and location algorithm.

This paper is organised as follows. The wavelet transform is explained in detail and the equations are given in "Wavelet transforms" section. The transformer model and parameter calculation are presented in section "Transformer winding model"". The case study used to simulate the fault signal and evaluate the algorithm are described in "Case studies and system characteristic" section. "Neural network decision algorithm and simulation results" section presents the results of the proposed fault location algorithm. Finally, the conclusions of the study are presented in "Conclusions" section.

The wavelet transform is similar to conventional methods such as the Fourier transform, but it has advantages over the Fourier transform for the analysis of transients resulting from faults in power systems. The reason is that the desired information in this type of application lies in both the frequency and time domains. The DWT has been used to analyse signals obtained from systems. A wavelet is a small localised wave of finite duration with a particular shape and an average value of zero. The wavelet transform is a tool that divides data, functions, or operators into different frequency components and then studies each component with a resolution suitable for its scale31,32. The transform enables fine adjustment of the band being analysed so that the high- and low-frequency components are detected accurately. The wavelet transform can expand signals using a shift in time or a translation as well as by compression in time or the dilation of a fixed wavelet function called the mother wavelet. Wavelet transforms in which the analysis is scaled by a factor of two are called DWTs and are written as follows.

where \(\psi \left[ {\frac{{n - k2^{m} }}{{2^{m} }}} \right]\) is the mother wavelet.

The Daubechies 4 (db4) mother wavelet was selected for the DWT because of its suitability for analysing transients in power systems14,30,31,32.

A two-winding three-phase transformer with separate primary and secondary windings for each phase was used in this study. An internal fault in the transformer was simulated by modifying the BCTRAN subroutine in the ATP/EMTP software30. BCTRAN typically uses a 6 × 6 inductance matrix to represent a transformer; however, because the internal fault condition (specifically, a winding-to-ground fault) is considered here, a 7 × 7 matrix was used33. The model was validated and its accuracy was proven by comparison with measurement results. However, the effects of high-frequency components that may appear during faults are not included in this model. The fault types and fault locations have been shown to affect the frequency responses of the transformer34. In addition, it has been proved that transient-based protection using the high-frequency components of fault currents can be used to locate and classify faults in transmission lines35. Therefore, it is useful to investigate the high-frequency components superimposed on the fault current signals to develop a transient-based protection system for a transformer. Thus, in this study, the transformer model proposed by Bastard et al.33 (Fig. 2) is combined with a high-frequency model recommended by an IEEE working group36, which includes the capacitances of the transformer (Fig. 3). The model is used to simulate winding-to-ground faults on the transformer windings.

ATP/EMTP model of power transformer with winding-to-ground fault33.

Diagram of two-winding transformer showing the effects of stray capacitances36.

The process for simulating winding-to-ground faults based on the BCTRAN routine of EMTP can be summarised as follows.

First step: Compute matrices R and L of the power transformer from the manufacture test data37 without considering winding-to-ground faults33, as shown in Eqs. (2) and (3).

Second step: Modify Eqs. (2) and (3) to obtain the new internal winding fault matrices \(\left[ R \right]^{*}\) and \(\left[ L \right]^{*}\), as shown in Eqs. (4) and (5), respectively33.

Third step: Simulate the interwinding capacitance and earth capacitance of the high- and low-voltage windings by adding the lumped capacitance connected to the terminals of the transformer.

The ATP/EMTP software30 was used to simulate the system signal under normal and fault conditions (sampling rate: 200 kHz, sampling time: 5 μs) The substation used in this case study was modelled after a portion of the 115 kV EGAT transmission system that is connected to a 23 kV Provincial Electricity Authority (PEA) distribution line. The power transformer used in this substation is a two-winding, three-phase step-down transformer (50 MVA, 115/23 kV); the configuration and specifications supplied by the manufacturer37 were used. Figure 4 shows a single-line diagram of the power transformer and connected components. In addition, the configuration of the parameter in power transformer that using in the case study can be summarize as shown in Table 1. A thorough simulation was performed to evaluated the proposed algorithm under various conditions. The parameters of the simulations are as follows.

Primary and secondary windings (high- and low-voltage coils) with various phases in which a fault occurs were used.

The inception angle of the fault signal (the phase A voltage is used as a reference) was varied from 0° to 330° in steps of 30°.

The fault location on the winding, measured as the distance from the terminal of the coil, was varied from 10 to 90% in steps of 10%.

The fault resistance was 5 Ω.

Single-line diagram of transmission line section used in case study.

Faults in power systems significantly affect the current signal, which thus can be used to determine whether a fault has occurred in the system. Thus, the proposed fault detection algorithm is based on the application of the DWT to the three-phase current waveform obtained from measurement devices on both the primary and secondary sides of the power transformer. Figures 5 and 6 show examples of the three-phase current signal obtained from the primary and secondary sides for a fault from winding phase A to ground in the primary (high-voltage) winding and secondary (low-voltage) winding, respectively, using the ATP/EMTP software30.

Primary and secondary currents under phase A winding-to-ground fault occurrence on the high-voltage winding at 10% of the length.

Primary and secondary currents under phase A winding-to-ground fault occurrence on the low-voltage winding at 10% of the length.

During the fault, the current of the fault phase on the primary side increased significantly owing to current flow through the fault location. By contrast, the current on the secondary side decreased because less power was transferred owing to the fault on the primary side. However, a fault on the secondary side caused a small transient and a smaller decrease in the current measured from the secondary side. This behaviour can be used to diagnosis the fault status of the system.

The current signals obtained from the primary and secondary sides of the power transformer were used to calculate the differential current. The three-phase current was also transformed into the positive-, negative-, and zero-sequence current. The quarter-cycle of the three-phase current and zero-sequence waveform after fault inception were used as input. The wavelet transform extracts waveform coefficients of scale 1 to scale 5. The coefficient value is extracted from the signal and then squared to emphasized the change in the coefficient value, as shown in Figs. 7 and 8 for faults on the primary and secondary winding, respectively.

Coefficients of three-phase and zero-sequence differential currents under phase A winding-to-ground fault on high-voltage (primary) winding at 10% of the length.

Coefficients of three-phase and zero-sequence differential currents under phase A winding-to-ground fault on low-voltage (secondary) winding at 10% of the length.

The extracted coefficients show a strong peak when a fault occurs in the system and then decrease to the normal level. This behaviour results from the properties of wavelets, which react during transients but not in the steady state. The coefficient output of the wavelet transform was used to construct the decision algorithm by trial and error. The algorithm was applied using coefficients of different scales, and the scale-1 coefficients were found to be sufficiently distinct for the algorithm to identify internal fault inception. Thus, only the scale-1 coefficients obtained from the DWT were used as training data for the neural network to obtain a fast algorithm.

Artificial intelligence, in particular neural networks, has been widely applied in various fields, including electrical engineering. The BPNN is a neuron-based structure that is suitable for pattern recognition and fault classification. It consists of three layers: an input layer, at least one hidden layer, and an output layer. These layers are connected by weights and biases. The proposed algorithm uses a BPNN architecture with one input layer, two hidden layers, and one output layer, as shown in Fig. 9.

BPNN used in proposed algorithm.

Two hidden layers are used in the neural network structure for the algorithm because of the functional advantage over a structure with one hidden layer. However, different activation functions also provide a wide range of accuracy for the algorithm. Thus, suitable activation functions for the fault location algorithm for a power transformer were selected. The hyperbolic tangent sigmoid, logistic sigmoid, and linear functions were considered. Table 2 lists the 12 combinations of activation functions used in the hidden and output layers.

The training process for the BPNN can be divided into three parts, as follows38.

Feedforward input pattern

The feedforward input pattern propagates data from the input layer to the hidden layer and finally to the output layer. The response from the input pattern can be calculated using Eqs. (6) and (7).

where.

p = input vector of BPNN,

iw1,1 = weights between input layer and first hidden layer,

lw2,1 = weights between first and second hidden layers,

lw3,2 = weights between second hidden layer and output layer,

b1, b2 = bias in first and second hidden layers, respectively,

b3 = bias in output layer,

f1, f2 = activation function (hyperbolic tangent sigmoid function: tanh),

f3 = activation function (linear function).

Back-propagation of associated error

The associated error of a BPNN is the error between the neural network and target outputs. It is propagated to all the neurons in the layer below and is also used as a reference for the adjustment of the weights and biases.

Weight and bias adjustment

The weights and biases were adjusted using the Levenberg–Marquardt (trainlm) process to match the calculated and target outputs. The mean absolute percentage error (MAPE) index was used to determine the efficiency of the BPNN; it is calculated using Eq. (8).

where n is the number of test sets.

The proposed structure of the BPNN based on calculation results consists of four neuron inputs, two hidden layers, and one neuron output. The input pattern of the neural network consists of the scale-1 maximum coefficients (cD1) of the three-phase and zero-sequence currents from the post-fault differential currents. The output variables of the neural network structure are labelled 0.1 to 0.9 depending on the location at which the winding-to-ground fault occurs. The input data sets are normalised and divided into 216 sets for training and 108 sets for testing. To train the neural network, the number of neurons in both hidden layers was increased, and different combinations of activation functions were used to select those with the best performance. The weights and biases were adjusted before the MAPE was computed, and the training cycle was repeated for 20,000 iterations to determine the best MAPE value. Training was stopped when the first hidden layer reached the final number of neurons or the MAPE of the test sets was less than 0.5%. Figure 10 shows a flowchart of the proposed BPNN training process.

Flowchart of BPNN training process.

After the training process, the BPNN-based decision algorithm was tested using the weight and bias that yielded the minimum MAPE. The stored data were then computed using only the input values, not the target output or calculated values similar to the correct target output. The number of case study and dataset that will be used as an input for the proposed algorithm can be summarize as shown in Table 3. Figure 11 shows the results obtained using various combinations of activation functions and the test set data on both the high- and low-voltage windings.

Average errors in fault location for different combinations of activation functions.

Four combinations of activation functions were found to provide accurate results with an average error below 5%:

Hyperbolic tangent–logistic–linear

Hyperbolic tangent–hyperbolic tangent–linear

Logistic–logistic–linear

Logistic–hyperbolic tangent–linear

After the training process, the algorithm was implemented in the system, and its performance in locating faults was evaluated using the winding-to-ground fault signal. A total of 324 cases under different conditions were examined to verify the algorithm performance and identify suitable combinations of activation functions. Table 4 lists the average error in fault location obtained using the four combinations of activation function that exhibited the best performance.

The four optimal activation function combinations have similar errors for the high-voltage winding. However, for the low-voltage winding, the combination hyperbolic tangent–hyperbolic tangent–linear can achieve higher accuracy with significantly less error than the other combinations.

Figure 12 shows the average error in fault location for different combinations of activation functions for the high- and low-voltage windings from phase A to phase C. The average error in fault location for the high-voltage winding is 2.5%, whereas that of the low-voltage winding is 6% at various lengths of the transformer winding. These results indicate the performance of each activation function under different conditions. The hyperbolic tangent–hyperbolic tangent–linear combination may not provide the best accuracy under some fault conditions, such as fault locations at 10% and 20% of the length on the low-voltage winding. However, it can provide the best accuracy on average for locating winding-to-ground faults.

Average error in fault location using four optimal activation function combinations.

Table 4 and Fig. 12 show that hyperbolic tangent–hyperbolic tangent–linear is a suitable combination of activation functions. Thus, it was selected as the activation function combination in the BPNN for locating winding-to-ground faults. Figure 13 shows the average error in fault location when the algorithm with these activation functions was applied. For various fault locations on both the high- and low-voltage windings of the three-phase transformer, the accuracy of fault location based on the prediction of the decision algorithm was excellent. The effects of various parameters on the performance of the proposed algorithm are shown in Tables 5, 6, 7, 8.

Average error in fault location when algorithm is used with hyperbolic tangent–hyperbolic tangent–linear activation functions.

Tables 5 and 6 show the predicted fault location and its error for winding-to-ground faults in phase A on the high- and low-voltage windings, respectively. The actual fault location was fixed at 10% of the length of the winding, and the inception angle of the fault signal was varied. The algorithm predicted the fault location on the high-voltage winding with an error of less than 3% for all inception angles. The prediction for the low-voltage winding was less accurate than that for the high-voltage winding. However, the overall error was below 5%. Thus, the inception angle does not significantly affect the performance of the proposed fault location algorithm.

Tables 7 and 8 list the predicted fault location and its error for winding-to-ground faults in phase A with a fixed inception angle and various fault locations on the high- and low-voltage windings, respectively. The inception angle was fixed at 240° for the high-voltage winding and 210° for the low-voltage winding. The algorithm predicted the fault location with errors of less than 1% for the high-voltage winding. The prediction was again less accurate for the low-voltage winding than for the high-voltage winding. However, the overall error was below 3%. These results demonstrate that the algorithm can locate faults accurately at every possible location.

The application of the proposed fault location method to different winding-to-ground faults in a power transformer revealed that the algorithm can detect faults accurately with errors of less than 0.5%. The fault location, inception angle, and winding voltage do not affect the performance of the algorithm. This study demonstrated that the proposed algorithm can be implemented in power transformer protection systems to provide operation and maintenance crews at electrical utilities with accurate information to respond to faults in power transformers quickly and correctly.

Power transformers are an essential component in power systems and can be vulnerable to faults, especially internal fault. Thus, a protection system is needed to accurately identify and isolate faults to minimise equipment damage. In addition, the ability to locate faults helps maintenance and operation crews to correctly respond to faults and ensure network reliability. The proposed algorithm uses a combination of the DWT and BPNN to locate winding-to-ground faults in a three-phase power transformer. The scale-1 maximum coefficients of the three-phase post-fault differential current signals and zero-sequence current were used as input to train the BPNN. Case studies of faults under different conditions were used to evaluate the performance of the proposed algorithm. The results demonstrated that the algorithm can detect and locate winding-to-ground faults using the activation function combination hyperbolic tangent–hyperbolic tangent–linear in various layers of the BPNN. The overall accuracy of the proposed algorithm exceeds 95%, and in some cases the accuracy reaches 99.5%. In addition, the fault location performance was not affected by various system parameters. This technique should be useful in identifying and repairing winding-to-ground faults in power transformers. In future work, the algorithm will be improved so that the locations of interturn faults along the windings of the transformer can be identified.

The datasets used and analysed during the current study available from the corresponding author on reasonable request.

Christina, A. J. et al. Causes of transformer failures and diagnostic methods—A review. Renew. Sustain. Energy Rev. 82(1), 1442–1456 (2018).

Google Scholar

Faiz, J. & Heydarabadi, R. Diagnosing power transformers faults. Russ. Electr. Eng. 85(12), 785–793 (2015).

Article Google Scholar

Horowitz, S. H., Phadke, A. G. & Niemira, J. K. Power System Relaying 4th edn. (Wiley, New York, 2013).

Google Scholar

de Faria Jr, H., Costa, J. G. S. & Olivas, J. L. M. A review of monitoring methods for predictive maintenance of electric power transformers based on dissolved gas analysis. Renew. Sustain. Energy Rev. 46, 201–209 (2015).

Article Google Scholar

Senobari, R. K., Sadeh, J. & Borsi, H. Frequency response analysis (FRA) of transformers as a tool for fault detection and location: A review. Electr. Power Syst. Res. 155, 172–183 (2018).

Article Google Scholar

Soni, R. & Mehta, B. Review on asset management of power transformer by diagnosing incipient faults and faults identification using various testing methodologies. Eng. Fail. Anal. 128, 105634 (2021).

Article Google Scholar

Ballal, M. S., Suryawanshi, H. M., Mishra, M. K. & Chaudhari, B. N. Interturn faults detection of transformers by diagnosis of neutral current. IEEE Trans. Power Delivery 31(3), 1096–1105 (2016).

Article Google Scholar

Ehsanifar, A. et al. Transformer inter-turn winding fault detection based on no-load active power loss and reactive power. Int. J. Electr. Power Energy Syst. 130, 107034 (2021).

Article Google Scholar

Bagheri, S., Moravej, Z. & Gharehpetian, G. B. Classification and discrimination among winding mechanical defects, internal and external electrical faults, and inrush current of transformer. IEEE Trans. Industr. Inf. 14(2), 484–493 (2018).

Article Google Scholar

Raichura, M., Chothani, N., Patel, D. & Mistry, K. [2_TD$DIFF] total harmonic distortion (THD) based discrimination of normal, inrush and fault conditions in power transformer. Renew. Energy Focus 36, 43–55 (2021).

Article Google Scholar

Zhang, C. et al. Transformer fault diagnosis method using IoT based monitoring system and ensemble machine learning. Future Gener. Comput. Syst. 108, 533–545 (2020).

Article Google Scholar

Pham, D. A. K., Pham, T. M. T., Borsi, H. & Gockenbach, E. A new diagnostic method to support standard frequency response analysis assessments for diagnostics of transformer winding mechanical failures. IEEE Electr. Insul. Mag. 30(2), 34–41 (2014).

Article Google Scholar

Satish, L. & Sahoo, S. K. Locating faults in a transformer winding: An experimental study. Electr .Power Syst. Res. 79(1), 89–97 (2009).

Article Google Scholar

Klomjit, J., Ngaopitakkul, A. & Sreewirote, B. Comparison of mother wavelet for classification fault on hybrid transmission line systems. In 8th IEEE International Conference on Awareness Science and Technology (iCAST 2017). 527–532 (2017).

Pothisarn, C. et al. Comparison of various mother wavelets for fault classification in electrical systems. Appl. Sci. 10, 1–15 (2020).

Article Google Scholar

Medeiros, R. P. & Costa, F. B. A wavelet-based transformer differential protection with differential current transformer saturation and cross-country fault detection. IEEE Trans. Power Deliv. 33(2), 789–799 (2018).

Article Google Scholar

Cheng, Q., Zhao, Z., Tang, C., Qian, G. & Islam, S. Diagnostic of transformer winding deformation fault types using continuous wavelet transform of pulse response. Measurement 140, 197–206 (2019).

Article ADS Google Scholar

Aires, M. N. O. et al. A wavelet-based restricted earth-fault power transformer differential protection. Electr. Power Syst. Res. 196, 107246 (2021).

Article Google Scholar

Gururajapathy, S. S., Mokhlis, H. & Illias, H. A. Fault location and detection techniques in power distribution systems with distributed generation: a review. Renew. Sustain. Energy Rev. 74, 949–958 (2017).

Article Google Scholar

Rumkidkarn, J., Ngaopitakkul, A. Behavior analysis of winding to ground fault in transformer using high and low frequency components from discrete wavelet transform. In 2017 International Conference on Applied System Innovation (ICASI), 1102–1105 (2017).

Shah, M. & Bhalja, B. R. Discrimination between internal faults and other disturbances in transformer using the support vector machine-based protection scheme. IEEE Trans. Power Deliv. 28(3), 1508–1515 (2013).

Article Google Scholar

Beheshtaein, S. Application of wavelet-base method and DT in detection of ferroresonance from other transient phenomena. In 2012 International Symposium on Innovations in Intelligent Systems and Applications. (2012).

Fernandes, J. F., Costa, F. B. & de Medeiros, R. P. Power transformer disturbance classification based on the wavelet transform and artificial neural networks. In International Joint Conference on Neural Networks (IJCNN). 640–646 (2016).

Bhasker, S. K., Bera, P. K., Kumar, V. & Tripathy, M. Differential protection of indirect symmetrical phase shift transformer and internal faults classification using wavelet and ANN. TENCON 2015—2015 IEEE Region 10 Conference. 1–6 (2015).

Ngaopitakkul, A. & Bunjongjit, S. An application of a discrete wavelet transform and a back-propagation neural network algorithm for fault diagnosis on single-circuit transmission line. Int. J. Syst. Sci. 44(9), 1745–1761 (2013).

Article MATH Google Scholar

Kaitwanidvilai, S., Pothisarn, C., Jettanasen, C., Chiradeja, P. & Ngaopitakkul, A. Discrete wavelet transform and back-propagation neural networks algorithm for fault classification in underground cable. In International MultiConference of Engineers and Computer Scientists 2011 (IMECS 2011). 996–1000 (2011).

Zin, A. A. M., Saini, M., Mustafa, M. W., Sultan, A. R. & Rahimuddin,. New algorithm for detection and fault classification on parallel transmission line using DWT and BPNN based on Clarke's transformation. Neurocomputing. 168, 983–993 (2015).

Article Google Scholar

Ngaopitakkul, A., Jettanasen, C., Asfani, D. A. & Negara, Y. Application of discrete wavelet transform and back-propagation neural network for internal and external fault classification in transformer. Int. J. Circuits Syst. Signal Process. 13, 458–463 (2019).

Google Scholar

Bunjongjit, S. & Ngaopitakkul, A. Selection of proper artificial neural networks for fault classification on single circuit transmission line. Int. J. Innov. Comput. Inf. Control. 8(1A), 361–374 (2012).

MATH Google Scholar

ATPDraw https://www.atpdraw.net/index.php (2022).

Kim, C. H. & Aggarwal, R. Wavelet transforms in power systems: Part I. General introduction to the wavelet transforms. IEE Power Eng. J. 14(2), 81–87 (2000).

Article Google Scholar

Makming, P., Bunjongjit, S., Kunakorn, A., Jiriwibhakorn, S. & Kando, M. Fault diagnosis in transmission lines using wavelet transforms. In IEEE Transmission and Distribution Conference. 2246–2250 (2002).

Bastard, P., Bertrand, P. & Meunier, M. A transformer model for winding fault studies. IEEE Trans. Power Delivery 9(2), 690–699 (1994).

Article Google Scholar

Islam, S. M. & Ledwich, G. Locating transformer faults through sensitivity analysis of high frequency modeling using transfer function approach. In IEEE International Symposium on Electrical Insulation. 38–41 (1996).

Bo, Z. Q., Redfern, M. A. & Weller, G. C. Positional protection of transmission line using fault generated high frequency transient signals. IEEE Trans. Power Delivery 15(3), 888–894 (2000).

Article Google Scholar

IEEE working group 15.08.09. Modeling and analysis of system transients using digital programs (IEEE PES special publication, 2009)

ABB Thailand, Test report no. 56039.

Demuth, H. & Beale, M. Neural Network Toolbox User's Guide (The Math Work, 2001).

Download references

Faculty of Engineering, Srinakharinwirot University, Bangkok, Thailand

Pathomthat Chiradeja

School of Engineering, King Mongkut's Institute of Technology Ladkrabang, Bangkok, Thailand

Atthapol Ngaopitakkul

You can also search for this author in PubMed Google Scholar

You can also search for this author in PubMed Google Scholar

A.N. Performed the analysis and wrote the main manuscript text and prepared figures and tables. P.C. Contributed data, and analysis tools, reviewed the manuscript. All authors reviewed the manuscript.

Correspondence to Atthapol Ngaopitakkul.

The authors declare no competing interests.

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.

Reprints and Permissions

Chiradeja, P., Ngaopitakkul, A. Winding-to-ground fault location in power transformer windings using combination of discrete wavelet transform and back-propagation neural network. Sci Rep 12, 20157 (2022). https://doi.org/10.1038/s41598-022-24434-9

Download citation

Received: 29 April 2022

Accepted: 15 November 2022

Published: 23 November 2022

DOI: https://doi.org/10.1038/s41598-022-24434-9

Anyone you share the following link with will be able to read this content:

Sorry, a shareable link is not currently available for this article.

Provided by the Springer Nature SharedIt content-sharing initiative

By submitting a comment you agree to abide by our Terms and Community Guidelines. If you find something abusive or that does not comply with our terms or guidelines please flag it as inappropriate.